The cart is empty.
Your Trusted Partner for Expert Security Solutions.
DWG

1000224 Potter ATC-4 Auto Test Four Zone Test Control

SKU: 1000224

VSR-AT Series

Auto-Test Waterflow Alarm Switch with Electronic Retard

The Model VSR-AT is an electronic vane type waterflow switch for use on wet sprinkler systems which may be remotely tested without flowing water. It is UL Listed and FM Approved for use on steel pipe schedules 10 thru 40 sizes 2" thru 8". See ordering Information chart. The VSR-AT may also be used as a sectional waterflow detector on large systems. The VSR-AT has two sets of alarm contacts and an adjustable instantly recycling electronic retard. The alarm contacts are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard time.

The VSR-AT may be remotely tested without flowing water by using the optional auto test Control model ATC-1 or ATC-4 or the use of addressable relays and monitor modules as part of a listed addressable fire alarm panel.

When the auto test feature is initiated, the VSR-AT performs a self test to ensure compliance with UL requirements regarding waterflow detection and retard time. In addition, the auto test feature ensures the integrity of the paddle/trip stem assembly. A successful completion of the auto test will activate both sets of normally open contacts on the flow switch. If the auto test detects a problem with the trip stem/paddle assembly or if there is no water in the pipe, neither normally open contact will operate and the flow switch will indicate a trouble condition at the test switch and transmit a trouble signal to the fire alarm panel.

Potter's Auto-ITM line of products set a new benchmark in fire safety maintenance by automating inspection, testing, and maintenance processes to boost reliability and safety. This innovative approach reduces human error, cuts down labor costs, and enhances compliance, ensuring fire protection systems remain operational and up to code. For building owners, facility managers, and contractors, Auto-ITM delivers peace of mind, streamlining operations and supporting consistent system readiness. Embracing Auto-ITM means embracing a future where efficiency and safety lead the way in fire system maintenance.

More details...
MPN: 1000224
Ordering Notes: Service Professionals Only
MSRP Price: $244.00
Online Price: $244.00
Save to my Wish List

New to DWG? - Sign Up for immediate access to dealer pricing and benefits.

Already a DWG Customer? - Sign In to view pricing.



Product Details

Related Video - A look at Potter's Wet Corrosion Solutions

Related Video - How to Wire a Potter VSR-AT AutoTest Flow Switch

Related Video - VSR-AT - Normal Waterflow Event

Related Video - VSR-AT - Auto Test with Water Present

Related Video - VSR-AT - Auto Test without Water Present

Features

  • Assembled in USA
  • Can be remotely tested without flowing water
  • 0-90 second electronic retard
  • UL Listed and FM approved models for 2"-8" steel pipe schedules 10 through 40
  • Two SPST contacts
  • Weatherproof
  • Easy to read wire terminal designations

Description

The model VSR-AT is an electronic vane type waterflow switch for use on wet sprinkler systems. It is UL Listed and FM Approved for use on steel pipe schedules 10 thru 40 sizes 2” thru 8”. See ordering Information chart.

The VSR-AT may also be used as a sectional waterflow detector on large systems. The VSR-AT has two sets of alarm contacts and an adjustable instantly recycling electronic retard. The alarm contacts are actuated when a flow of 10 GPM (38 LPM) or more occurs downstream of the device. The flow condition must exist for a period of time necessary to overcome the selected retard time.

The VSR-AT may be remotely tested without flowing water by using the optional auto test Control model ATC-1or ATC-4 or the use of addressable relays and monitor modules as part of a listed addressable fire alarm panel.

When the auto test feature is initiated, the VSR-AT performs a self test to ensure compliance with UL requirements regarding waterflow detection and retard time. In addition, the auto test feature ensures the integrity of the paddle/trip stem assembly. A successful completion of the auto test will activate both sets of normally open contacts on the flow switch. If the auto test detects a problem with the trip stem/paddle assembly or if there is no water in the pipe, neither normally open contact will operate and the flow switch will indicate a trouble condition at the test switch and transmit a trouble signal to the fire alarm panel.

Enclosure

The VSR-AT switches and retard device are enclosed in a general purpose, die-cast base and a weather/UV/flame resistant high impact composite cover. The cover is held in place with two tamper resistant screws which require a special key for removal.

Technical Specifications

  • Conduit Entrances -Two knockouts provided for 1/2" conduit. Individual switch compartments suitable for dissimilar voltages
  • Contact Ratings
    • Two sets of SPDT (Form C)
    • 10.0 Amps at 125/250VAC
    • 2.0 Amps at 30VDC Resistive
    • 10 mAmps min. at 24VDC
  • Enclosure - Cover - Weather/UV/Flame Resistant High Impact Composite Base - Die-cast aluminum
  • Environmental Specifications - NEMA 4/IP54 Rated Enclosure suitable for indoor or outdoor use with factory installed gasket when used with appropriate conduit fitting. Temperature Range: 40°F - 120°F, (4.5°C - 49°C) - UL Non-corrosive sleeve factory installed in saddle
  • Flow Sensitivity Range for Signal - 4-10 GPM (15-38 LPM) - UL
  • Maximum Surge - 18 FPS (5.5 m/s)
  • Power Requirements - 24 VDC From Listed or Approved Source With Battery Backup
  • Service Pressure - 450 PSI (31 BAR) - UL
  • Service Use
    • Automatic Sprinkler NFPA-13
    • One or two family dwelling NFPA-13D
    • Residential occupancy up to four stories NFPA-13R
    • National Fire Alarm Code NFPA-72

1000224 Specifications PDF


Product Reviews

Write your own review

 

Rate this product: