DWG

1000275 Potter STN-5 5' Sampling Tube For Analog Addressable Duct Detector

SKU: 1000275

PAD200-DUCT Series

Analog Addressable Duct Detector

The PAD200-DUCT is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7”) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws.

Enhanced sensor technology allows the PAD200 Detector Series to comply with the new UL 268 7th edition standards while bringing customers an even higher standard in smoke detection.

More details...
MPN: 1000275
Ordering Notes: Service Professionals Only
MSRP Price: $44.00
Price: $44.00
Save to my Wish List

New to DWG? - Sign Up for immediate access to dealer pricing and benefits.

Already a DWG Customer? - Sign In to view pricing.



Product Details

Features

  • Detects smoke in building HVAC ducts
  • Ships complete with housing and head
  • Compatible with addressable IPA and AFC/ARC series panels
  • SLC in and out wire terminals
  • SLC Class A, Class X & Class B
  • Installation without removing the head
  • Listed Air Velocity of 100 to 4,000 ft/minute
  • No screens or filters in housing
  • Durable plastic enclosure and clear cover
  • Integrated cover tamper switch
  • Utilizes simple snap in sampling tubes STN series
  • Product includes a 5 year warranty
  • UUKL Listed for Smoke Control

Description

The PAD200-DUCT is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors. Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7”) is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws.

Application

The Potter Electric PAD200-DUCT duct smoke detector provides early detection of smoke and products of combustion present in air moving through HVAC ducts in commercial, industrial and residential applications. The PAD200-DUCT is compatible with the IPA and AFC/ARC series addressable fire alarm control panels

Engineering Specification

Air duct smoke detectors shall be Potter Electric PAD200-DUCT Series. The detectors shall be listed by Underwriters Laboratories per UL 268A. The detectors shall operate at air velocities from 100 feet per minute to 4000 feet per minute. The duct detector housings shall be of plastic construction and complete mechanical installation may be performed without removal of detector cover. Visual indication of alarm and power must be provided on detector front. Detector heads shall not require additional filters or screens which must be maintained. The housing shall contain a detector base and PAD200-DD duct smoke detector head. Terminal connections shall be of the screw type and be a minimum of # 12 screw. All wiring must comply with local codes and regulations. Detector shall use the STN series of sampling tubes.

Specifications

  • Duct Detector Model Number - PAD200-DUCT
  • Operating Voltage - 24 VDC
  • Current Draw - 300 μA
  • Detector Head Model - PAD200-DD
  • Detector Head Type - Photoelectric
  • Alarm Set Point - Fixed at 2.5%/ft
  • Sensitivity Test Method - Self diagnostic test
  • Air Velocity - 100 to 4000 ft./min
  • Ambient Temperature - 32°F to 120°F (0°C to 49°C)
  • Humidity - 10% to 85% Relative humidity (non- condensing)
  • Housing Material - Plastic backbox, clear plastic cover
  • Finish - Gray backbox with clear cover
  • Dimensions - 13 1/2”L x 4 1/2” W x 2 1/4” H
  • Maximum Net Weight - 2 lbs
  • Sampling Tubes - 2.5 ft., 5 ft., or 10 ft