Features
- Up to 2 Detector Heads reporting to One Ground Level Controller
- Range of 26.2 ft to 328 ft (8 m to 100 m)
- Long range prism kit extends range from 160ft (50m) to 330ft (100m)
- Built in Laser assisted prism mounting
- Auto-Alignment 2 to 4 minutes per head
- AutOptimise: Auto-Correction due to building shift
- Built-in electronic UL/ULC/FM obscuration-acceptance fire test
- Contamination compensation
- Separate Trouble and Alarm relays for each of the 2 channels
- Password protected settings
Low current draw 5 to 8.5mA- Built-in 1/2â€/M-20 conduit knock-outs on the system controller
- Programmable alarm thresholds: 10% - 60% in 1% increments
- Programmable Fault and Alarm delay: 2-30 Seconds
Description
The Fireraye 5000 System is an auto-aligning, self-correcting infrared reflective beam smoke detector. Up to 2 detector heads can report to a single ground level controller. In addition, each system controller houses two pairs of fire and trouble relays, one per detector. Once the detector head is installed, using the easyfit mounting system an integral LASER can be activated. This allows the reflective prism to be located quickly and with confidence.
The Auto-Align function ensures proper alignment and maximum signal during the beam installation. AutoOptimise automatically steers and maintains the beam in the optimum position for reliable performance. The signal generated in the transmitter element and reflected by the prism back to the receiver element is analyzed for the presence of smoke. The internal microprocessor determines an alarm condition when a predetermined level obscuration is reached.
The system is designed to be mounted so the beam will project between 19" (0.5m) and 24" (0.6m) below the ceiling. Lateral detection may be up to 30ft. (9.144m) on either side of the beam, providing a maximum total coverage area of up to 19,800 square feet (60ft. x 330ft. or I 8.29m x I OOm). For installations complying with UL268/NFPA72, the maximum distance of Detector and Reflector from the ceiling must be 10% of the distance between floor and ceiling.
Engineering Specification
The projected beam type smoke detector shall be listed to U.L. 268 and shall consist of up to two integrated transmitter, receiver detector heads and single low level remote control unit. The detector shall operate between a range of 26.2 ft to 328 ft (8 m to 100 m). The temperature range of the system shall be -4°F to 131 °F (-20°C to 55°C). The beam detector heads shall include an integral built-in laser pointer to assist prism mounting. The beam detector shall feature automatic gain control which will compensate for gradual signal deterioration from dirt accumulation on the lenses and prisms. The beams detector heads shall include AutoOptimise self-correcting motorized head feature to ensure unit is always receiving maximum signal available, and shall automatically compensate for building shift. The unit shall include a low level remote display and control unit with LCD read-out for set-up, reporting and testing of up to 2 separate detector heads. The System shall have separate Trouble and Alarm relays for each of the 2 channels.
The system shall be capable of programming alarm thresholds of 10% to 60% in 1% increments. The system shall be capable of programming delay to fault and delay to alarm from 2 seconds to 30 seconds in I second increments. Test and acceptance of the system shall be carried out by using the UQULC/FM approved internal electronic obscuration fire test. The projected beam type smoke detector shall be a 4-wire 24 VDC device to be used with a separately supplied 4-wire control panel. The Reflective beam type smoke detector shall be a FFE Ltd Freray 5000.
Construction Specifications
- Housing: - Flame Retardant PC UL94 V0
- IP Rating: - IP54
- Finish: - Light Grey/Black
- Weight: - Head & Controller 3.24 lbs (1.47 kg)
- Dimensions: - Head: 5.28†H x 5.16†L x 5.28†W (134mm H x 131mm L x 134mm W), Controller: 3.43†H x 9.06†L x 7.95†W (87mm H x 230mm L x 202mm W), Prism: 0.37†H x 4.13†L x 3.94†W (9.5mm H x 105mm L x 100mm W)
Electical Specifications
- Primary Input Power: - 14 to 36 VDC
- Standby Current: - Low Current Mode: 5mA to 8.5mA @ 24VDC depending on number of detector heads used High Current Mode: 37mA @ 24VDC
- Alarm Current: - 5mA to 8.5mA @ 24VDC depending on number of detector heads used
- Relay Contacts: - 1A @ 30VDC Resistive
- Reset Time: - 5 Seconds maximum
- Start Up Time: - 45 Seconds
- Optical Wavelength: - 850nm
- Alarm Threshold: - 10% - 60% (35% Default)
- Temperature Rating: - -4°F to 131°F (-20°C to 55°C) For UL Listed Installations: 32°F to 100°F (0°C to 38°C)
- Relative Humidity: - 0% to 93% RH non-condensing
- Range: - 26.2 ft to 328 ft (8 m to 100 m)
- Cabling Between each Detector & Controller: - 18-14 AWG 1-Pair
1430143 Specifications PDF