The cart is empty. 4 Total: $10,081.00
Your Trusted Partner for Expert Security Solutions.
DWG

1030001 Potter PAAR-B Automatic Air Release with Drip Pan

SKU: 1030001

PAAR-B Series

Automatic Air Release with Drip Pan

The PAAR-B is an automatic float type air vent used to reduce the amount of air trapped in a pressurized fire sprinkler system. Reducing the amount of air in a fire sprinkler system is essential to help protect the system piping from the effects of corrosion that is often found at the air/water interface in the fire sprinkler system piping.

Removing as much air as possible will also have a positive effect on the performance of vane type waterflow detectors. The operation of vane type waterflow detectors can be delayed or prevented if too much air is trapped in the system piping.

The intent of the product is to vent as much air from the fire sprinkler system as possible. The PAAR-B provides automatic venting of air as the system is being filled. Furthermore, trapped air can also be vented as the air in the system migrates to the vent location over time. The air vent will automatically close when water reaches the vent.

Discharge piping from the air vent valve is piped to a shutoff valve mounted in a water retention pan. The pan retains small amounts of water discharged from the air vent valve during normal operation. If failure of the air vent occurs, discharged water will reach a specified depth in the pan (approximately 1") and a water-soluble fiber element in the shutoff valve dissolves and closes the valve preventing further water discharge. The shutoff valve has a visual indication of operation and a single set of NC contacts rated 24V AC/DC@2A for electronic supervision (Recommended). The shutoff valve is a single-use device and contains no user serviceable parts.

The PAAR-B provides a 1/2" NPT connection in the bottom of the pan which shall be used to pipe to a drain.

Potter's Auto-ITM line of products set a new benchmark in fire safety maintenance by automating inspection, testing, and maintenance processes to boost reliability and safety. This innovative approach reduces human error, cuts down labor costs, and enhances compliance, ensuring fire protection systems remain operational and up to code. For building owners, facility managers, and contractors, Auto-ITM delivers peace of mind, streamlining operations and supporting consistent system readiness. Embracing Auto-ITM means embracing a future where efficiency and safety lead the way in fire system maintenance.

More details...
MPN: 1030001
Ordering Notes: Service Professionals Only
MSRP Price: $1,911.00
Online Price: $1,911.00
Save to my Wish List

New to DWG? - Sign Up for immediate access to dealer pricing and benefits.

Already a DWG Customer? - Sign In to view pricing.



Product Details

Features

  • UL Listed for Fire Sprinkler Branch line applications per UL subject 2573—”Automatic Air Release Valves for Fire Protection Service”
  • FM Approved for “Automatic Air Release Valve for Sprinkler Systems”
  • Provides water retention pan and secondary positive stop shutoff valve eliminating any possibility of water discharge

Description

The PAAR-B is an automatic float type air vent used to reduce the amount of air trapped in a pressurized fire sprinkler system. Reducing the amount of air in a fire sprinkler system is essential to help protect the system piping from the effects of corrosion that is often found at the air/water interface in the fire sprinkler system piping.

Removing as much air as possible will also have a positive effect on the performance of vane type waterflow detectors. The operation of vane type waterflow detectors can be delayed or prevented if too much air is trapped in the system piping.

The intent of the product is to vent as much air from the fire sprinkler system as possible. The PAAR-B provides automatic venting of air as the system is being filled. Furthermore, trapped air can also be vented as the air in the system migrates to the vent location over time. The air vent will automatically close when water reaches the vent.

Discharge piping from the air vent valve is piped to a shutoff valve mounted in a water retention pan. The pan retains any inadvertent water that may discharge during the venting process. If failure of the air vent occurs, discharged water will reach a specified depth in the pan (approximately 1”) and a water-soluble fiber element in the shutoff valve dissolves and closes the valve preventing further water discharge. The shutoff valve has a visual indication of operation and a single set of NC contacts rated 24V AC/DC@2A for electronic supervision (Recommended). The shutoff valve is a single-use device and contains no user serviceable parts.

The PAAR-B provides a 1/2” NPT connection in the bottom of the pan which can be used to pipe to a drain.

Technical Specifications

  • Service Pressure - Up to 175 PSIG
  • Environmental Limitations - Indoor Use Only 40°F to 120°F (4.5°C to 49°C)
  • PAV - Potter Air Vent - 1/2” NPT inlet, 5/64” Orifice, UL Listed, FM Approved, Brass Construction
  • Water Shutoff Valve - Activation indicated by red pop-up tab on the shutoff valve. Single set of NC contacts rated 24V AC/DC at 2A (contacts open upon activation of shutoff valve) and 6’ Lg. wiring harness supplied for supervision of shutoff valve
  • Optional Accessories - Ball valve supervisory switch Model RBVS (Supervisory switch only). Used to monitor the position of the isolation valve.