Supervised Zone Module
The Potter PVX-ZM Supervised Zone Module is used in conjunction with the PVX Series Voice Evacuation Panels to provide separately supervised and protected circuits from a single speaker output. The EVX-ZM is default configured for 4 Class B circuits, but may be converted to 2 Class A with the flip of a switch. The PVX-ZM can be ganged together to provide a maximum of 64 Class B circuits.
The PVX-ZM in standard operating mode is strictly All Call. On any page, alarm, or message function all circuits activate. If separate zoning is required, the PVX-ZM has zone selection inputs which may be activated by a N.O. dry contact. Additionally, the PVX-SL8(LED Switch Card) may be employed to provide both Zone and Message selection by switch.
Each speaker circuit employs smart power metering to insure short circuit conditions are isolated from the other circuits. Each circuit is rated 50W @ 70V and 40W @ 25V.
New to DWG? - Sign Up for immediate access to dealer pricing and benefits.
Already a DWG Customer? - Sign In to view pricing.
The potter pVX-SL8 LeD Switch Module provides switch selection for message activation, paging, and control functions.
When used in conjunction with the PVX-ZM zone module, the SL8 can be programmed for page zone control. LeDs for switches assigned to page zones will indicate Red for page and flashing Red for alarm. The LED will indicate amber if the associated speaker circuit is in a fault condition.
Switches can be programmed to control corresponding points on the PVX-OL8. Switch LeDs will indicate steady Red on activation.